Instructions for the installer
17
13.INSTALLATION OF THE APPLIANCE
It is the law that all gas appliances are installed by authorised persons. Clearance around the cooker
must comply with the requirements of AS5601.
13.1 Electrical connection
Make sure that the power line voltage matches the specifications indicated on the rating plate located
inside the storage compartment.
This rating plate must never be removed.
On the power line, install a two-pole cut-off device with contact cut-off distance greater than or equal to 3
mm, located in an easily accessible position near the unit.
The connection terminals are located at the rear of the
appliance. For electrical connections see following
diagram. To access, remove the rear cover.
For operation on 380-415V3N (only for 90 cm models): use an
H05RR-F / H05RN-F / H05V2V2-F type five-core cable (5 x 1.5
mm
2
).
For operation on 380-415V2N (only for 90 cm models): use an
H05RR-F / H05RN-F / H05V2V2-F type five-core cable (cavo di 4 x
1.5 mm
2
)
For operation on 220-240V : use an H05RR-F / H05RN-F /
H05V2V2-F (3 x 2.5 mm
2
).
The cable end to be connected to the appliance must be provided
with an ground wire (yellow-green) at least 20 mm longer.
The manufacturer declines all responsibility for damage to persons or things caused by non-
observance of the above prescriptions.